Conductive Level Control
Over view
Liquid Level Controller Controls maximum and/or minimum levels of conductive liquids 'Pump-up' or 'Pump-down' modes selectable via switch Adjustable sensitivity 5-100kΩ Response times 100ms (high level); 500ms (low level) One or two probe operation Low voltage, ac current across probes prevents electrolysis phenomena LED indication for supply and relay status Ambient temperature; -20 to +60°C DIN rail mounting, W45mm Write-on identification tab Dimensions (mm): H 75, W 45, D 99
Note 1. If using metal tank, connect "com" and earth to the tank 2. If supply is interrupted for ≤0.5s in "pump-up" mode, the relay will energise immediately. In "pump-down" mode relay remains de-energised 3. For single probe operation, link terminals "com" and "max"
|