The M200-PB1 can detect the following conditions in phase 3 or 4 wire systems. Phase Unbalance, Phase Loss, Phase Reversal and Phase Sequence. The phase balance relays are used to detect phase loss and unbalance in systems using motors, generators, heater elements, transformers etc. A Phase unbalance as small as 10% in a 3 phase motor can cause the temperature in the motor winding to increase by more than 120%, correct setting of the PB1/PB2 will ensure this does not occur. Protection against open phase regenerated voltage, created if a single phase should fail is also provided. Customer adjustment of unbalanced voltage between 5 to 15% is provided along with time delay adjustment of 200ms to 10 seconds. If the system being monitored is healthy, the relay is energized, and the red LED will be illuminated. If a phase unbalance greater than the pre-set level or phase loss / reversal occurs, the relay de-energizes after the time delay period. The M200-PB2 provides all the protection features of the PB1 with the additional benefit of having symmetrical under voltage protection. This means that if all the phase voltages remain balanced but drop below a pre-set value, the relay will de-energize. The under voltage is internally set. For standard units it is set at 85% below the nominal voltage, but this value can optionally be between 70% and 90%
|