1154 TMF Insulation & Multifunction Tester (LCD)

SKU:
1154TMF
$560.00

● Microprocessor-controlled.
● Automatic voltmeter AC/DC at Start/Reset.
● Auto range
● Auto-off: Approx. 5 minutes.
● Safety voltmeter before each test.
● Auto discharge on all test and all ranges.
● Leads Auto-Null key.
● Test Auto-Stop.
● Smart hold & stop on voltmeter AC/DC.
● Battery test. Battery test at switch ON/Reset.
● Ener-Save feature to extend battery life.
● Continuity open circuit voltage of 5Vdc.
● Nominal voltage @ 1mA on all insulation ranges.
● BS 16 edition.

$560.00

Specifications

● Insulation Resistance
- Test voltage: 50V / 100V / 125V / 250V / 500V / 1000V.
- Measuring ranges: 0.1MΩ~400MΩ / 0.1MΩ~800MΩ / 0.1MΩ~1GΩ / 0.2M~2GΩ / 0.2M~4GΩ / 0.2M~8GΩ.
- Accuracy: 0.1MΩ~4GΩ: ±3%rdg. 4GΩ~8GΩ: ±5%rdg.
● MOVs & GAS Voltage Result @ 1mA
- Test Voltage: 5 ~ 1020V.
- Accuracy: ±3%rdg±2dgt.
● Continuity Short Circuit Current > 220mA
- Range: 0.01~100Ω / 100~300Ω / 300~1999Ω.
- Accuracy: ±1%rdg / ±1.5%rdg / ±2%rdg.
- Auto-Null Up to 5Ω.
- Buzzer Threshold Value Up to 3Ω.
● Voltmeter (Autoranging): 0~700VAC. 0~950VDC. - Resolution: ±1V.
- Accuracy: ±1.5% F.S.
- Auto-Hold.
● Battery load current: Approx. 300mA.
● LCD type: Large Type 2 × 16 Characters.
● Fuse: Fast HBC 500mA 600V (5 × 20mm).
● Operating temp.: 0°C to 40°C not in full sun.
● Storage temp.: -10°C to 50°C.
● Dimensions: 175(L) × 85(W) × 75(D)mm.
● Weight (battery included): Approx. 655g.
● Power source: 1.5V (AA) × 8 Alkaline (or rechargeable) batteries.
● Safety Standard: EN 61010-1 CAT III 600V. EN 61326-1.

Accessories: Instruction manual, Test leads, Shoulder belt, Soft pouch, Batteries.