Microprocessor-controlled.
2Lines × 16 Characters LCD.
Very low consumption.
Menu-driven.
Accurate digital readout of disconnection time.
Automatic data hold function.
Zero Crossing Circuitry permit testing at 0° or 180°.
Disconnection Phase Polarity shown on LCD display.
Auto-off and off override.
Accurate digital readout of disconnection sensitivity.
Polarity Trip indicator (Positive of Negative Phase).
Wiring polarity indicator.
Measure voltage and frequency between Line and Earth before testing.
Accessories
Instruction manual
Test leads
Shoulder belt
Batteries.
Current settings: 3mA, 5mA, 7mA, 10mA, 15mA, 20mA, 30mA, 35mA, 50mA, 100mA, 125mA, 150mA, 175mA, 250mA, 275mA, 300mA, 375mA, 500mA.
Current selection: Rotary switch selector
Phase start selection 0° and 180°: Referenced to Earth
Over-temperature protection: Yes (3 sensors)
Wiring correctness indication: Yes (LEDs)
Trip indicator: Yes (LEDs)
Phase polarity trip Indicator: Yes (LCD). Referenced to Earth
Voltmeter (L-E): 20 Vac to 280 Vac
Timer resolution: 1ms (Max. Time = 2.999s)
Timer accuracy: ±2% ±2ms
Current accuracy: ±5% ±1mA
Voltameter resolution: 1V
Voltmeter accuracy: ±2%±1Vac
General
Operating temperature: -5°C to 40°C
Storage temperature: -10°C to 55°C
Maximum current Specified at: 450 Vac/50Hz
Dimensions: 170(L) × 165(W) × 92(D)mm
Weight (battery included): Approx. 1020g
Power source: 1.5V (AA) × 8
Safety Standard
EN 61010-1 CAT III 240V
EN 61326-1