Microprocessor-controlled.
2 Lines × 16 characters LCD.
Very low consumption.
Suitable for domestic version.
Better than 3% accuracy (current).
Menu-driven.
Accurate digital readout of disconnection time.
Accurate digital readout of disconnection sensitivity.
Automatic data hold function.
Zero crossing circuitry permit testing at 0° or 180°.
Disconnection phase polarity shown on LCD display.
Auto off and off override.
Polarity trip indicator (positive or negative phase)
Wiring polarity indicator.
Measure voltage between Line and Earth before testing.
60Hz available.
Accessories
Instruction manual
Test leads
Shoulder belt
Batteries.
System voltage (50Hz / 60Hz): 550V | 380V | 240V
Current settings: 2-999mA ac
Current selection: Knob
Phase start selection referenced to earth: 0° and 180°
Over-temperature protection: Yes
Wiring correction indication: Yes
Phase polarity trip indicator: Yes
Operating voltage (L-E): 110 Vac to 317 Vac
Timer resolution: 1ms (Max. Time=19.999s)
Timer accuracy: 1ms ±1ms
Current accuracy: ±1% ±1mA
Current resolution: 1mA
Voltmeter resolution: 1V
Voltmeter resolution: ±2%±1Vac
Voltmeter accuracy (50Hz):
- 50-350 Vac: ±2%±1V
- 350-450 Vac: ±5%±1V
General
Operating temperature: -5°C to 40°C
Storage temperature: -10°C to 55°C
Dimensions: 170(L) × 165(W) × 92(D)mm
Weight (battery included): Approx. 1300g