High quality Taut Band movement.
Three insulation test voltages(DC) : 250V, 500V, 1000V.
Two continuity test on low ohms : 3Ω & 500Ω.
Compact and lightweight.
200mA continuity short circuit current.
1mA test current on insulation test at nominal voltage.
Automatic discharge of capacitive and inductive circuit with charge stored in the circuit under test.
Live warning and display or external voltage presence.
Fuse, air gap, crowbar and overload protected.
On line battery monitoring shows if battery is ok.
Manual zero ohm adjustment.
Low battery consumption.
Mirror scale.
Push and turn locking switch for continuous and hand free testing.
BS 16 edition.
Accessories
Instruction manual,
Test leads,
Batteries,
Shoulder belt.
Insulation Resistance
Test voltage (DC V): 250V / 500V / 1000V
Output voltage on open circuit: Rated test voltage +10%
Measuring ranges: 0-100MΩ / 0-200MΩ / 0-400MΩ
Mid-scale value: 1MΩ / 2MΩ / 4MΩ
Scale multiplier: ×1/2 / ×1 / ×2
Accuracy: ± 5% of indicated value
Output short circuit current: ≥ 1.0mA
Continuity
Measuring range: 3Ω / 500Ω
Output short circuit current: ≥200 mA
Accuracy: ± 1.5% of scale length
AC Voltage
Range: 0-600V
Accuracy: ± 3% of scale length
Warning light circuit live lit From 90Vdc / 70Vac, Buzzer beep from 24V ac/dc
Battery check indicate good batteries from 8Vdc to 13Vdc during a load test of 240mA.
Battery OK LED lit from 8Vdc and is operative while testing
General
Dimensions: 210(L) × 210(W) × 100(D)mm
Weight (battery included): Approx. 1400g
Power source: 1.5V (AA) × 8
Safety Standard
EN 61010-1 CAT III 600V
EN 61326-1