Overload: Momentary - 10 X rated current, 10 consecutive intervals of 1/2 second with a 1 minute interval between successive applications; sustained - 20% for 6 hours.
Accuracy: ±2% full scale value.
Resistance: ±15%.
Movement: AC Current Movement.
Dials: 100 or 90 degree arc, black lettering on white background.
Pointer: Knife Edge.
Case: Non-static phenolic.
General
Operating Temperature: 32°F to 104°F (0°C to 40°C).
Storage Temperature: -4°F to 131°F (-20°C to 55°C).
Relative Humidity: 20% to 80%RH (Nominal Use).
Meter Approvals: ANSI C39.1, RoHS, REACH.
Origin: Made in USA.
Part Number |
Range |
Scale |
Term Resistance |
|
2736/10MAAC
2736/30MAAC
2736/50MAAC
2736/100MAAC
2736/150MAAC
2736/200MAAC
2736/300MAAC
2736/500MAAC
|
FS = 10MAAC
FS = 30MAAC
FS = 50MAAC
FS = 100MAAC
FS = 150MAAC
FS = 200MAAC
FS = 300MAAC
FS = 500MAAC
|
0-10MAAC
0-30MAAC
0-50MAAC
0-100MAAC
0-150MAAC
0-200MAAC
0-300MAAC
0-500MAAC
|
2800
400
103
36
25
14
4.8
3.4
|
|
2736/1AAC
2736/3AAC
2736/5AAC
2736/10AAC
2736/15AAC
2736/25AAC
2736/30AAC
2736/50AAC
|
FS = 1AAC
FS = 3AAC
FS = 5AAC
FS = 10AAC
FS = 15AAC
FS = 25AAC
FS = 30AAC
FS = 50AAC
|
0-1AAC
0-3AAC
0-5AAC
0-10AAC
0-15AAC
0-25AAC
0-30AAC
0-50AAC
|
0.271
0.053
0.130
0.003
0.003
0.003
0.002
0.001
|
|
Other Ranges available upon request. Custom dials, input and illumination available.