Loop impedance range L-E, L-N: 20/200/2000Ω (auto-range).
Loop impedance test current: 12A at 230V / 50Hz.
Voltage measurement L-N, L-E: 80 to 250V AC/50Hz
Earth wire/path return resistance: 20/200/2000Ω (auto-range).
Neutral wire return resistance: 20/200/2000Ω (auto-range).
Line wire return resistance & transformer windings: 20/200/2000Ω (auto-range).
PSC current (L-N) max: 3kA.
Operating voltage: 230V±20V / 50Hz.
Typical Accuracy
Loop impedance: ±5%rdg ± 2dgt.
PSC current: ±20%rdg ± 5dgt.
Voltage: ±1%rdg ±1dgt.
General
Operating temperature / humidity: -10°C to +40°C 80% Max. relative humidity.
Dimensions: 170(L) x 120(W) x 95(D)mm.
Weight (battery included): Approx. 780g.
Power source: 1.5V (AA) x 8.
Accessories
Instruction manual,
Test leads,
Shoulder belt,
Batteries.
Safety Standard
EN 61010-1 CAT III 600V
EN 61326-1