Microprocessor-controlled.
Operating voltage 100-450V L-E.
Rated current 999mA, at 317V AC/50Hz.
Checks ELCB trip time and trip point (sensitivity).
Auto off and auto ranging.
Phase angle selection(0° / 180°).
Indicates tripping phase angle.
Impact resistant enclosure.
Over temperature shut-down.
Transient protection.
Suitable for heavy industrial use.
Fused.
Accessories
Instruction manual
Test leads
Shoulder belt
Batteries.
Trip current-range: 0-1A at 317V (Auto-Rang Programmable)
Trip current-resolution: 1mA
Operating voltage (L-E): 100 - 450V
Phase angle setting: 0° and 180° selectable
Timer-max: 99.999s
Timer resolution: 1ms
Typical Accuracy
- Trip-current: ±1%rdg±1mA
- Trip-time: ±1%rdg±1dgt
- Voltage: ±3%rdg±1dgt
General
Operating temperature / humidity: -10°C to +40°C / 80% Max. relative humidity
Dimensions: 170(L) × 120(W) × 95(D)mm
Weight (battery included): Approx. 800g
Power source: 1.5V (AA) × 8
Safety Standard
EN 61010-1 CAT III 450V
EN 61326-1