AC Ranges: Milliammeter, Ammeter, Voltmeter, Frequency Meter, Motor Load Meter.
Overload:
Voltmeter (AC and DC): 50% momentary 20% sustained.
Ammeter (AC and DC) momentary: 10 times the rated current for 10 consecutive intervals of .5 seconds with a 1 minute interval between successive applications; 20% for six hours.
Accuracy: ±2% full scale value.
Resistance: ±15%.
Movement: Pivot and Jewel, AC Iron Vane or Taut Band.
Dials: 100 or 90 degree arc, black lettering on white background.
Pointer: Knife Edge.
Case: Lexan.
Mounting: Specify (S) Surface mount, (B) Bezel mount or (W) Window mount.
General
Operating Temperature: 32°F to 104°F (0°C to 40°C).
Storage Temperature: -4°F to 131°F (-20°C to 55°C).
Relative Humidity: 20% to 80%RH (Nominal Use).
Meter Approvals: ANSI C39.1, RoHS, REACH, UL Recognized meters available.
Origin: Made in USA.
Part Number |
Range |
Scale |
Term Resistance |
AC MILLIAMMETER |
3146/10MAAC
3146/30MAAC
3146/50MAAC
3146/100MAAC
3146/150MAAC
3146/200MAAC
3146/300MAAC
3146/500MAAC
|
FS = 10MAAC
FS = 30MAAC
FS = 50MAAC
FS = 100MAAC
FS = 150MAAC
FS = 200MAAC
FS = 300MAAC
FS = 500MAAC
|
0-10MAAC
0-30MAAC
0-50MAAC
0-100MAAC
0-150MAAC
0-200MAAC
0-300MAAC
0-500MAAC
|
2800
400
103
36
25
14
4.8
3.4
|
AC AMMETER |
3146/1AAC
3146/3AAC
3146/5AAC
3146/10AAC
3146/15AAC
3146/25AAC
3146/30AAC
3146/50AAC
|
FS = 1AAC
FS = 3AAC
FS = 5AAC
FS = 10AAC
FS = 15AAC
FS = 25AAC
FS = 30AAC
FS = 50AAC
|
0-1AAC
0-3AAC
0-5AAC
0-10AAC
0-15AAC
0-25AAC
0-30AAC
0-50AAC
|
0.271
0.053
0.130
0.003
0.003
0.003
0.002
0.001
|
AC VOLTMETER |
3146/10VAC
3146/15VAC
3146/25VAC
3146/30VAC
3146/50VAC
3146/100VAC
3146/150VAC
3146/300VAC
3146/500VAC
3146/600VAC
|
FS = 10VAC
FS = 15VAC
FS = 25VAC
FS = 30VAC
FS = 50VAC
FS = 100VAC
FS = 150VAC
FS = 300VAC
FS = 500VAC
FS = 600VAC
|
0-10VAC
0-15VAC
0-25VAC
0-30VAC
0-50VAC
0-100VAC
0-150VAC
0-300VAC
0-500VAC
0-600VAC
|
360
75
1315
1630
9100
16100
26100
51100
83600
96100
|
AC FREQUENCY METER |
Part Number |
Frequency |
Voltage |
|
3146/45-55HZ/120ACV 3146/55-65HZ/240ACV
|
45-55HZ 55-65HZ
|
120ACV 240ACV
|
|
AC MOTOR LOAD METER |
3146/ML
|
Percent Motor Load current, alternating current. |
|
Other Ranges available upon request. Custom dials, input and illumination available. Please contact us for pricing and availability.