Capable of measuring earth resistance and earth voltage.
2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.
In addition to facilitating for precision measurement, test leads for simplified two-wire measuring system also are supplied as standard accessories.
Battery operated.
Battery life indicator.
Calibration performed with supplied test leads.
Accessories
Instruction manual
Test leads (red-15m, yellow-10m, green-5m)
Auxiliary earth spikes
Simplified measurement probe
Shoulder belt
Batteries.
Measuring system: Earth resistance by constant current inverter 820 Hz, 2mA approx.
Open circuit indication: LED will be unlit
Measuring ranges:
- Earth resistance: 0-12Ω / 0-120Ω / 0-1200Ω
- Earth voltage: 0-30 Vac (40-500Hz)
Accuracy:
- Earth resistance ±3% of full scale
- Earth voltage ±2.5% of full scale
General
Dimensions: 250(L) × 190(W) × 110(D)mm
Weight (battery included): Approx. 1500g
Power source: 1.5V (AA) × 8
Safety Standard
EN 61010-1 CAT III 300V