Microprocessor-controlled.
2 Lines × 16 Characters LCD.
Very low consumption.
Menu-driven.
Accurate digital readout of disconnection time.
Automatic data hold function.
Zero Crossing Circuitry permit testing at 0° or 180°.
Disconnection Phase Polarity Shown on LCD.
Auto off and off override.
Polarity Trip indicator (Positive or Negative Phase).
Wiring polarity indicator.
Measure voltage between line and earth before testing.
Indicates frequency of voltage L-E.
Accessories
Instruction manual
Test leads
Shoulder belt
Batteries.
Current settings: 3mA, 5mA, 7mA, 10mA, 15mA, 20mA, 30mA, 35mA, 50mA, 100mA, 125mA, 150mA, 175mA, 275mA, 250mA, 300mA, 375mA, 500mA.
Current selection: Rotary switch.
Phase start selection: 0° and 180°.
Referenced to Earth: Yes.
Over-temperature protection: Yes.
Wiring correctness indication: Yes.
Trip indicator: Yes.
Phase polarity trip Indicator: Yes.
Operating voltage (L-E): Referenced to Earth 240Vac-50Hz or 60Hz, Voltage Model (Vac).
Timer resolution: 1ms (Max. Time=2.999s).
Timer accuracy: 1ms ±1ms.
Current accuracy: ±5% ±1mA.
General
Operating temperature: -5°C to 45°C.
Storage temperature: -10°C to 55°C.
Dimensions: 250(L) × 190(W) × 110(D)mm.
Weight (battery included): Approx. 1500g.
Power source: 1.5 (AA) × 8.
Safety Standard
EN 61010-1 CAT III 300V
EN 61326-1.