Industrial Series was designed to meet industrial requirements and for other applications where cases with glass fronts provide long service under adverse conditions.
High current ammeter ranges with external shunt are available, as are special or non-standard ranges.
Special Dials are available with the following options: Additional Colors, Scales, Special Legends, Logo and Mirrors.
Available with or without illumination.
Overload:
Momentary - 10 X rated current, 10 consecutive intervals of 1/2 second with a 1 minute interval between successive applications;
Sustained - 20% for 6 hours.
Accuracy: ±2% full scale value.
Resistance: ±10%.
Dials: 90 or 100 degree arc, black lettering on white background.
Pointer: Knife Edge.
Movement: AC Current Movement.
Mounting: Surface Mount.
Case: Phenolic and ABS Plastic.
General
Operating Temperature: 32°F to 104°F (0°C to 40°C).
Storage Temperature: -4°F to 131°F (-20°C to 55°C).
Meter Approvals: ANSI C39.1, RoHS, REACH.
Origin: Made in USA.
Part Number |
Range |
Scale |
Term Resistance |
|
552P/10MAAC
552P/30MAAC
552P/50MAAC
552P/100MAAC
552P/150MAAC
552P/200MAAC
552P/300MAAC
552P/500MAAC
|
FS = 10MAAC
FS = 30MAAC
FS = 50MAAC
FS = 100MAAC
FS = 150MAAC
FS = 200MAAC
FS = 300MAAC
FS = 500MAAC
|
0-10MAAC
0-30MAAC
0-50MAAC
0-100MAAC
0-150MAAC
0-200MAAC
0-300MAAC
0-500MAAC
|
2800
400
103
36
25
14
4.8
3.4
|
|
552P/1AAC
552P/3AAC
552P/5AAC
552P/10AAC
552P/15AAC
552P/25AAC
552P/30AAC
552P/50AAC
|
FS = 1AAC
FS = 3AAC
FS = 5AAC
FS = 10AAC
FS = 15AAC
FS = 25AAC
FS = 30AAC
FS = 50AAC
|
0-1AAC
0-3AAC
0-5AAC
0-10AAC
0-15AAC
0-25AAC
0-30AAC
0-50AAC
|
0.271
0.053
0.130
0.003
0.003
0.003
0.002
0.001
|
|
Other Ranges available upon request. Custom dials, input and illumination available.