Industrial Series was designed to meet industrial requirements and for other applications where cases with glass fronts provide long service under adverse conditions.
High current ammeter ranges with external shunt are available, as are special or non-standard ranges.
Special Dials are available with the following options: Additional Colors, Scales, Special Legends, Logo and Mirrors.
Available with or without illumination.
Overload:
Momentary - 10 X rated current, 10 consecutive intervals of 1/2 second with a 1 minute interval between successive applications;
Sustained - 20% for 6 hours.
Accuracy: ±2% full scale value.
Resistance: ±10%.
Dials: 100 degree arc, black lettering on white background.
Pointer: Knife Edge.
Movement: AC Current Movement.
Mounting: Specify (F) Flush or (S) Surface Mount.
Case: Phenolic and ABS Plastic.
General
Operating Temperature: 32°F to 104°F (0°C to 40°C).
Storage Temperature: -4°F to 131°F (-20°C to 55°C).
Meter Approvals: ANSI C39.1, RoHS, REACH.
Origin: Made in USA.
Part Number |
Range |
Scale |
Term Resistance |
|
636/10MAAC 636/30MAAC 636/50MAAC 636/100MAAC
636/150MAAC 636/200MAAC 636/300MAAC 636/500MAAC
|
FS = 10MAAC FS = 30MAAC FS = 50MAAC FS = 100MAAC
FS = 150MAAC FS = 200MAAC FS = 300MAAC FS = 500MAAC
|
0-10MAAC 0-30MAAC 0-50MAAC 0-100MAAC
0-150MAAC 0-200MAAC 0-300MAAC 0-500MAAC
|
2800 400 103 36 25
14 4.8 3.4
|
|
636/1AAC 636/3AAC
* 636/5AAC/0-5AAC * 636/5AAC/0-50AAC * 636/5AAC/0-100AAC * 636/5AAC/0-150AAC * 636/5AAC/0-200AAC
* 636/5AAC/0-300AAC * 636/5AAC/0-500AAC * 636/5AAC/0-750AAC * 636/5AAC/0-1KAAC * 636/5AAC/0-1.5KAAC
* 636/5AAC/0-2KAAC * 636/5AAC/0-2.5KAAC * 636/5AAC/0-3KAAC
636/10AAC 636/15AAC 636/25AAC 636/30AAC 636/50AAC
|
FS = 1AAC FS = 3AAC
FS = 5AAC FS = 5AAC FS = 5AAC FS = 5AAC FS = 5AAC
FS = 5AAC FS = 5AAC FS = 5AAC FS = 5AAC FS = 5AAC
FS = 5AAC FS = 5AAC FS = 5AAC
FS = 10AAC FS = 15AAC FS = 25AAC FS = 30AAC FS = 50AAC
|
0-1AAC 0-3AAC
0-5AAC 0-50AAC 0-100AAC 0-150AAC 0-200AAC
0-300AAC 0-500AAC 0-750AAC 0-1KAAC 0-1.5KAAC
0-2KAAC 0-2.5KAAC 0-3KAAC
0-10AAC 0-15AAC 0-25AAC 0-30AAC 0-50AAC
|
0.271 0.053
0.130 0.130 0.130 0.130 0.130
0.130 0.130 0.130 0.130 0.130
0.130 0.130 0.130
0.003 0.003 0.003
0.002 0.001
|
|
* - Current transformer required.
Other Ranges available upon request. Custom dials, input and illumination available.
Please contact us for pricing and availability.