Industrial Series was designed to meet industrial requirements and for other applications where cases with glass fronts provide long service under adverse conditions.
High current ammeter ranges with external shunt are available, as are special or non-standard ranges.
Special Dials are available with the following options: Additional Colors, Scales, Special Legends, Logo and Mirrors.
Available with or without illumination.
DC Ranges: Microammeters, Milliammeters, Ammeters, Millivoltmeters, Voltmeters.
Overload
- Voltmeters (AC and DC): 50% momentary 20% sustained.
- Ammeters (AC and DC) momentary: 10 times the rated current for 10 consecutive intervals of .5 seconds with a 1 minute interval between successive applications; 20% for six hours.
Accuracy: ±2% full scale value.
Resistance: ±10%.
Dials: 100 degree arc, black lettering on white background.
Pointer: Knife Edge.
Movement: Pivot and Jewel, Iron Vane or Taut Band.
Mounting: Specify (F) Flush or (S) Surface Mount.
Case: Phenolic and ABS plastic.
General
Operating Temperature: 32°F to 104°F (0°C to 40°C).
Storage Temperature: -4°F to 131°F (-20°C to 55°C).
Meter Approvals: ANSI C39.1, RoHS, REACH.
Origin: Made in USA.
Part Number |
Range |
Scale |
Term Resistance (self shielded) |
Term Resistance (ext magnet) |
DC Microammeters |
647/20UADC
647/50UADC
647/100UADC
647/200UADC
647/500UADC
647/25-0-25UADC
647/50-0-50UADC
647/100-0-100UADC
647/500-0-500UADC
|
FS = 20UADC
FS = 50UADC
FS = 100UADC
FS = 200UADC
FS = 500UADC
FS = 25-0-25UADC
FS = 50-0-50UADC
FS = 100-0-100UADC
FS = 500-0-500UADC
|
0-20UADC
0-50UADC
0-100UADC
0-200UADC
0-500UADC
25-0-25UADC
50-0-50UADC
100-0-100UADC
500-0-500UADC
|
N/A
3900
2600
1000
230
3900
2600
1000
50
|
3500
2200
2200
900
200
2200
2200
900
60
|
DC Milliammeters |
647/1MADC
647/5MADC
647/10MADC
647/25MADC
647/50MADC
647/100MADC
647/150MADC
647/200MADC
647/300MADC
647/500MADC
|
FS = 1MADC
FS = 5MADC
FS = 10MADC
FS = 25MADC
FS = 50MADC
FS = 100MADC
FS = 150MADC
FS = 200MADC
FS = 300MADC
FS = 500MADC
|
0-1MADC
0-5MADC
0-10MADC
0-25MADC
0-50MADC
0-100MADC
0-150MADC
0-200MADC
0-300MADC
0-500MADC
|
50
8
3
0.66
0.55
0.27
0.16
0.14
0.14
0.6
|
50
8
3
0.66
0.55
0.27
0.16
0.14
0.14
0.6
|
DC Ammeters |
647/1ADC
647/3ADC
647/5ADC
647/10ADC
647/15ADC
647/25ADC
647/30ADC
647/50ADC
|
FS = 1ADC
FS = 3ADC
FS = 5ADC
FS = 10ADC
FS = 15ADC
FS = 25ADC
FS = 30ADC
FS = 50ADC
|
0-1ADC
0-3ADC
0-5ADC
0-10ADC
0-15ADC
0-25ADC
0-30ADC
0-50ADC
|
0.0500
0.0166
0.0100
0.0050
0.0033
0.0020
0.0017
0.0010
|
0.0500
0.0166
0.0100
0.0050
0.0033
0.0020
0.0017
0.0010
|
DC Millivoltmeters |
647/50MVDC
|
FS = 50MVDC
|
0-50MVDC
|
50
|
50
|
DC Voltmeters |
647/1VDC
647/3VDC
647/5VDC
647/10VDC
647/15VDC
647/25VDC
647/30VDC
647/50VDC
647/100VDC
647/150VDC
647/250VDC
647/300VDC
647/500VDC
647/600VDC
647/750VDC
|
FS = 1VDC
FS = 3VDC
FS = 5VDC
FS = 10VDC
FS = 15VDC
FS = 25VDC
FS = 30VDC
FS = 50VDC
FS = 100VDC
FS = 150VDC
FS = 250VDC
FS = 300VDC
FS = 500VDC
FS = 600VDC
FS = 750VDC
|
0-1VDC
0-3VDC
0-5VDC
0-10VDC
0-15VDC
0-25VDC
0-30VDC
0-50VDC
0-100VDC
0-150VDC
0-250VDC
0-300VDC
0-500VDC
0-600VDC
0-750VDC
|
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
2000 Ω PER VOLT
2000 Ω PER VOLT
2000 Ω PER VOLT
|
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
1000 Ω PER VOLT
2000 Ω PER VOLT
2000 Ω PER VOLT
2000 Ω PER VOLT
|
Other Ranges available upon request. Custom dials, input and illumination available. Please contact us for pricing and availability.