Bright three line four digit LED display that lets the user view multiple three phase power at one time to replace several single function meters.
Primary and Secondary potential transformers or current transformers can be programmed through the front panel or optional Modbus.
Current Demand, kVA Demand, kW Demand, kW Export Demand are setup to track power consumption and RPM measurement is available for generator applications.
Any of the parameters can be assigned to a limit switch for alarms.
MODBUS (RS-485) Communication (optional).
Pulse/Limit Switch output (optional).
3 Line 4 Digits ultra bright LED Display (up to 9999).
On site Programmable CT/PT Ratios.
User selectable CT Secondary 1A/5A
User selectable PT Secondary from 100 VLL to 500 VLL
Programmable Energy format & Energy rollover count
Wide auxillary Power Supply which can accept any input between 60V – 300V AC/DC or 20-40 VAC or 20-60 VDC
Display: 4 Digit Red LED.
Enclosure: IP50 Front or IP65 with Gasket.
Operating Temperature: -20 to 70°C.
Reference conditions for Accuracy
Reference Temperature: 23°C +/- 2°C.
Input Waveform: Sinusoidal (distortion factor 0.005).
Input frequency: 50 or 60 Hz ±2%.
Auxiliary supply voltage: Rated Value ±1%.
Auxiliary supply frequency: Rated Value ±1%.
Voltage Range: 20... 100% of Nominal Value.
Current Range: 10... 100% of Nominal Value.
Power: Cos phi / sin phi = 1 for Active / Reactive Power & Energy. 10... 100% of Nominal Current & 20... 100% of Nominal Voltage.
Power Factor / Phase Angle: 40... 100% of Nominal Current & 20... 100% of Nominal Voltage.
Accuracy
Voltage: ± 1% of Nominal Value.
Current: ± 1% of Nominal Value.
Frequency: 0.5% of mid frequency.
Active Power, Re-Active Power, Apparent Power: ± 1% of Nominal Value.
Active Energy, Reactive Energy, Apparent Energy: ± 1%.
Power Factor: 2% of Unity.
Phase angle: 2% of range.