For all heavy-current power system variables.
Upto 6 outputs (2A + 4D or 4A + 2D or 2A or 3A).
Input voltage up to 693 V (phase-to-phase).
Universal analogue outputs (programmable).
High accuracy: U/I 0.2%, Frequency 0.15% and P 0.25% (under reference conditions).
Universal digital outputs (meter transmitter, limits).
AC/DC power supply/universal (24-80V AC/DC or 85-230V AC/DC).
Windows software with password protection for programming, data analysis, power system status simulation, acquisition of meter data and making settings.
Input |
Wave form |
Sinusoidal |
Rated frequency |
50...60 Hz, 16 2/3 Hz |
Own consumption |
Voltage circuit < U2 / 400 kW
Condition: external power supply
Currenr circuit: 0.3 V A I / 5 A |
Digital outputs, pulse outputs, limit outputs |
Type of contact |
Open collector |
Number of pulses |
See “Ordering Information” |
Pulse Duration |
> 100 ms |
Interval |
> 100 ms |
Power supply |
8...40 V |
Output current |
ON 10...27mA | OFF < 2mA |
Safety |
Protection Class |
II |
Protection |
IP 40, housing | IP 20,terminals |
Overvoltage Category |
III |
Insulation Test |
Input voltage: AC 400 V | Input current: AC 400 V
Output: DC 40 V
Power supply: AC 400 V
DC 230 V |
Surge test |
5 KV, 1.2/50ms, 0.5 Ws |
Test voltages |
50Hz, 1min. ( DIN EN 61 010-1)
5550 V, Inputs versus all other circuits as well as outer surface
3250 V, Inputs circuits versus each other
3700 V, power supply versus outputs and SCI as well as outer surface 490V, outputs and SCI versus each other and versus
|
|
Power Supply
AC Voltage: 100. 110. 230, 400, 500 or 693 V, + 10%, 45 to 65 Hz. Power consumption approx 10 VA.
AC / DC power pack (DC and 50...60 HZ).
Installation Data
Housing: Housing T24 (see “Dimensioned drawings”).
Housing material: Lexan 940 (polycarbonate) Flammability Class V-o acc to UL 94, self extinguishing, non dripping, free of halogen with indirect wire pressure.
Mounting: For snapping onto top-hat rail(35X15 mm or 35X7,5mm) acc. to EN 50022 or directly onto a wall orpanel using the pull-out screw hole brackets.
Orientation: Any.
Weight Approx: With supply transformer approx, 1.1kg | With AC/DC power pack approx, 0.7kg
Ambient Conditions
Climatic rating: Climate class 3 acc to VDI / VDE3540.
Variations due to ambient temperature: + 0.1% / 10K.
Nominal range of use: 0...15...30...45°C (Usage group II) .
Storage temperature: -40 to +85 °C.
Relative humidity of annual mean: ≤ 75%