Universal measuring input.
Version: standard, with SD card, with Ethernet and internal memory.
Mathematical functions, i.e. median filter function on measured value.
Individual characteristic (up to 21 points).
1 or 2 (option) alarm output.
Built-in power supply of object transducers 24 V D.C. (option).
RS-485 interface Modbus RTU Slave, RTU Master or Monitor.
Modbus TCP Slave (option).
Possibility to record one measuring value and simultaneously up to 50 read-out/ written values via RS-485 Modbus Master.
Data recording in internal memory, up to 4MB or in external SD/SDHC card or internal file system memory (8 GB) (option).
Transducer programmable using buttons, eCon freeware (through RS-485 or Ethernet) or any web browser (through Ethernet).
Firmware upgradeable by the user.
Output
Analog: Current: 0/4...20 mA, load resistance < 500 Ω; Voltage: 0...10V, Load resistance > 500 Ω; Accuracy class: 0,1
Relay: 1 or 2 relays; voltageless contacts - NO - maximum load 5A 30V DC, 250V AC
Supplying output: 24 V DC / 30 mA (option)
Digital Interface
RS-485: Modbus RTU: 8N2, 8E1, 8O1, 8N1; Address 1...247. (Baud rate: 4.8, 9.6, 19.2, 38.4, 57.6, 115.2, 230.4, 256 kbit/s)
Rated Operation Conditions
Supply voltage: 85...253 V DC/AC (40...400Hz) | 20...40 V AC (40...400Hz) or 20...60 V DC
Power consumption 6 VA.
Temperature Ambient: -25...23...+55°C
Temperature Storage: -30...+70°C
Relative humidity: 25...95%. Inadmissible condensation
Working position: any
Safety & Compatibility Requirements
Electromagnetic Compability: Noise immunity, acc. EN 61000-6-2
Electromagnetic Compability: Noise emissions, acc. EN 61000-6-4
Isolation between circuits: Basic, acc. EN 61000-1
Pollution level: 2, acc. EN 61000-1
Installation category: III, acc. EN 61000-1
Maximal phase-to-earth voltage: for supply circuits 300 V, acc. EN 61000-1
Maximal phase-to-earth voltage: for other circuits 50 V, acc. EN 61000-1
Altitude above see level: < 2000 m.
External Features
Overal dimensions: 45 x 120 x 100 mm
Weight: 0.25 kg
Protection grade: for housing: IP40 / IP30, for terminals: IP20.
Readout field: LCD 2 x 8