High quality Taut Band movement.
Capable of measuring earth resistance and earth voltage.
2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.
Test test leads are supplied as standard accessories for simplified two-wire measuring system.
Battery operated.
Battery check function.
Calibration performed with supplied test leads.
Accessories
Instruction manual
Test leads (red-15m, yellow-10m, green-5m)
Auxiliary earth spikes
Simplified measurement probe
Carry case
Batteries.
Measuring system: Earth resistance by constant current inverter 820 Hz, 2mA approx.
Open circuit indication: LED will be unlit
Measuring ranges:
- Earth resistance: 0-10Ω / 0-100Ω / 0-1000Ω
- Earth voltage: 0-30 Vac (40-500Hz)
Accuracy
- Earth resistance ±3% of full scale
- Earth voltage ±2.5% of full scale
General
Dimensions: 205(L) × 90(W) × 55(D)mm
Weight (battery included): Approx. 514g
Power source: 1.5V (AA) × 6
Safety Standard: EN 61010-1 CAT III 30V